Welcome: Industrial Automation Parts
facebooktwitteryoutubelinkedin5

Allen Bradley

  • 20AD022A0AYNANC0 Allen Bradley PowerFlex 70 AC Drive
20AD022A0AYNANC0 Allen Bradley PowerFlex 70 AC Drive

20AD022A0AYNANC0 Allen Bradley PowerFlex 70 AC Drive

Product Description:

Product Details

IMG_3286.JPG

IMG_3284.JPG

Mechanical

Degree of protection (IP)IP20
Shock15 G peak for 11 ms duration (±1.0 ms)
Vibration0.152 mm (0.006 inch) displacement, 1 G peak

Electrical


Number of analogue outputs1
Mains voltage480 V
Integrated breaking resistanceNo
Internal dynamic brake resistors62 Ohm
Brake IGBTBrake IGBT installed
Bus undervoltage output shutoff437V DC @ 480V
Bus undervoltage fault level300V DC @ 480V
Internal communication moduleNo communication module
AC input undervoltage trip280V AC @ 480V
Bus voltage, nom648V DC @ 480V
Bus overvoltage trip810V DC @ 480V
Circuit breaker current rating, max80 A @ 480V AC, 3-phase
Motor circuit protector current rating, max30 A @ 480V AC, 3-phase
Output current rating, continuous22 A @ 480V AC, 3-phase
Output current rating, 1 min24.2 A @ 480V AC, 3-phase
Output current rating, 3 sec33 A @ 480V AC, 3-phase
Logic control ride-thru0.5 seconds minimum, 2 seconds typical
Brake resistorWithout drive mounted brake resistor
Input current rating19.9 A @ 480V AC, 3-phase
DocumentationManual
Carrier frequencyStandard control: 2, 3, 4, 5, 6, 7, 8, 9, and 10 kHz, vector control: 2, 4, 8, and 12 kHz, drive rating based on 4 kHz
Encoder quadrature90° ±27°
AC input overvoltage trip570V AC @ 480V
Input power rating8.3 kVA @ 480V AC, 1-phase
Dual element time delay fuse current rating25...45 A @ 480V AC, 3-phase
Non-time delay fuse current rating25...80 A @ 480V AC, 3-phase
Heat sink thermistorMonitored by microprocessor overtemp trip
Drive to motor power ratio, maxRecommended not greater than 2:1 ratio
Stop modesMultiple programmable stop modes including — Ramp, Coast, DC-brake, Fast brake, Ramp-to-hold and S-curve
Frequency accuracyDigital input: within ±0.01% of set output frequency
Acceleration/decelerationTwo independently programmable accel and decel times. Each time can be programmed from 0...3600 seconds in 0.1 second increments
Number of digital inputs6
Number of digital outputs2
Number of analogue inputs2
Internal watts loss34.2 W @ 480V, 15 Hp normal duty
Supporting protocol for DeviceNetYes
Human interface modelNo HIM-blank plate
Application in industrial area permittedYes
External watts loss305.4 W @ 480V, 15 Hp normal duty
Total watts loss339.6 W @ 480V, 15 Hp normal duty
Supporting protocol for EtherNet/IPYes
Mains frequency50 Hz
Output frequency rangeStandard control: 0...400 Hz, enhanced control: 0...500 Hz